After maximum sag or maximum wind deviation, the safe distance between overhead power line conductors and trees is as follows
The safe distance of 35- 1 10 kV overhead power line conductor at maximum sag is 4.0 meters; The safe distance of maximum wind deviation is 3.5 meters.
154-220kV overhead power line conductor has a safe distance of 4.5m at maximum sag and a safe distance of 4.0m at maximum wind deviation.
The safe distance of 330 kV overhead power line conductor at maximum sag is 5.5 meters; The safe distance of maximum wind deviation is 5.0 meters.
The safety distance of 500 kV overhead power line conductor at maximum sag is 7.0 meters; The safe distance of maximum wind deviation is 7.0 meters.
1- 10 kV overhead power line conductor's safe distance at maximum sag is 1.5(0.8) meters; The safe distance of maximum wind deviation is 2.0( 1.0) meters.
The safe distance of overhead power line conductors below 1 kV at maximum sag is 1.0(0.2) m; The safe distance of maximum wind deviation is 1.0(0.5) meters.
Note: Values of insulated wires are in brackets.
I hope our answer is helpful to you. If you have any other questions, please call the 24-hour power supply service hotline 95598 for consultation.